Product Introduction: P2000

Safe Inspection of Solar Installations with High Voltage

 

Solar installations (also known as photovoltaic or PV installations) are becoming increasingly high-voltage
in order to reduce costs and improve the efficiency of power generation systems.

 

As a result, it is important to select measuring instruments
that support higher voltage measurement to protect the safety of inspection workers.

 

The P2000 enables high voltage measurement up to CAT Ⅲ 2000 V
by simply connecting to a compatible Hioki clamp meter or digital multimeter.

 

Why is CAT III 2000 V capability necessary?

Recent years have seen the introduction of solar power systems and EV batteries that operate at progressively higher voltages, creating new maintenance demand. At the same time, the hazards posted by maintenance work are increasing due to use of higher voltages.

 

Safety standards categorize measurement locations by measurement category ratings CAT II, CAT III, and CAT IV based on their line-to-ground rated voltage, current capacity, and transient overvoltage. As part of a transition to a new standard (IEC61010-2-030:2017) in 2017, measurements of solar installations were classified as CAT III.

 

Against this backdrop, measuring instruments used in maintenance of solar installations must accommodate high voltages to ensure they can be used safely. Using instruments that can accommodate the appropriate measurement category serves to protect workers and equipment from serious accidents such as electric shock and burnout.

 

Currently, adoption of 1500 V solar installation is growing, but instruments that can accommodate even higher voltages will be necessary in the future as larger and even more efficient systems enter into use.

Hioki developed the P2000 to support CAT III 2000 V measurement in response to the near-term prospect of such applications.

P2000 Compatible Models

DIGITAL MULTIMETER
DT4261

AC/DC CLAMP METER
CM4375-50

To Be Released In
December 2021

AC/DC CLAMP METER
CM4373-50

To Be Released In
December 2021

AC/DC CLAMP METER
CM4371-50

To Be Released In
December 2021

AC/DC CLAMP METER
CM4141-50

To Be Released In
December 2021

P2000 Specifications

Maximum input voltage
(Max. rated voltage between INPUT H-INPUT L)

DC 2000 V

Maximum Rate Voltage to Earth

2000 V (Measurement CAT III)
1000 V (Measurement CAT IV)

Input Resistance

20 MΩ ±5.0% (between INPUT H – INPUT L, with OUTPUT terminal open)

Output ratio

Depends on the input impedance of the connected device (example: 1/10 when a device with an input impedance of 10 MΩ is connected)

Overload Protection

DC/AC 2200 V 1 minutes (between INPUT H – INPUT L)

DC/AC 600 V 1 minutes (between OUTPUT H – OUTPUT L)

OUTPUT terminal

4 mm banana terminal

Operating Environment

Indoor use, pollution degree 2, altitude up to 2000 m

Operating Temperature and
Humidity Range

Temperature: -25°C to 65°C

Humidity: -25°C to 40°C 80% RH or less (non-condensing)

From 40°C to 65°C:
40°C 80% RH or less to 65°C 25% RH or less
Linearly decreasing (non-condensing)

Storage Temperature and Humidity Range

-30° C to 70° C (-22º F to 158º F) 90% RH or less (non-condensing)

Applicable Standards

EN 61010

Product warranty period

3 years (probe body and cable part are not covered by warranty)

Accessories

Connection Cable Set L4943, Strap with buckle, Carrying Case C0205, Instruction Manual, Operating Precautions

Accuracy in combination with the DT4261 or Clamp Meter series

MODEL

COMBINATION ACCURACY SPECIFICATIONS

DT4261

±0.5% rdg ±5 dgt

CM4375-50

Range 600.0 V, ±1.0% rdg ±0.3 V
Range 2000 V, ±1.0% rdg ±3 V

CM4373-50

CM4371-50

CM4141-50